Posted by BigDumbDinosaur
Search Keys: lightning,grounding
Referencing: /Blog/B996.html
Grounding is everything, especially if building B gets its power from building A. Also, a high quality UPS (not the door stops made by APC!) is essential to protect hardware from power line hits. In areas frequented by lightning strikes, equipment should be powered by a ferroresonant UPS, which has far greater capacity to withstand strikes than a line interactive or double conversion unit.
In the only instance where a client of mine lost a system to lightning it was subsequently determined that the fatal strike had occurred to the roof of a storage building that was receiving power from the main office building via a local service drop (not a drop from a utility pole, but one strung between the buildings). This storage building has a metal roof and siding, and therefore is a natural lightning rod.
Anyhow, the bozo who wired the storage building did not bond the circuit breaker panel to a ground rod as required by the NEC. So when lightning came calling the energy of the strike saturated the metal structure with current, which passed into the guy wire supporting the service drop and then into the neutral of the main building. Due to the intense amperage involved, the neutral side, which normally should be at or very near ground potential, was suddenly raised to a very high voltage and like Sherman's army marching through Atlanta -- or, perhaps, driver ants munching their way through an African forest, the massive current flow burned up almost everything in its path. The entire computer system -- UNIX server, terminals, a PC, modem and the APC UPS -- was ruined.
This, incidentally, was the last time I installed an APC UPS in any system. My subsequent post mortem indicated that the actual voltage rise experienced at the input to the UPS should have been survivable. APC refused to make good on their advertised 25,000 dollar system protection, claiming that it didn't cover direct lightning hits to a building -- a caveat that I couldn't find anywhere in their warranty statement. My opinion of their products has not changed since then: a client of a friend of mine lost a system to a power line strike, which destroyed his APC UPS.
While on the subject of power issues, a sneaky source of trouble can be an effect I refer to as ground plane potential imbalance -- GPPI for short. Suppose you have a server in one location and a peripheral device -- a serial interface terminal, for example -- in another location. Each location gets its power from a different breaker panel.
In order for the server and terminal to exchange data, the signal grounds of each device must be connected together. It is customary design practice for the signal ground in each device to be bonded to chassis ground at some point, which means signal ground at both ends will be bonded to earth ground via each device's line cord (assuming the power receptacle itself has been properly grounded).
The problem is that even though ground is ground, small amounts of current may flow within the ground plane, resulting in GPPI. This happens because most grounding in interior electrical systems is obtained through the network of interconnected EMT (thinwall conduit), and not all joints are as solidly bonded as they should be. Also, neutral imbalance can occur -- often due to poor planning in the electrical system layout, which can cause some current to flow through the ground plane because neutral is always bonded to ground in a breaker panel.
If two interconnected devices -- our server and terminal in this case -- are at opposite ends of a GPPI situation, some of that stray current may flow through the ground lead in the data cable, causing the nominal logic levels to vary at twice the line frequency. This sort of voltage variation is not accounted for in the design of the device and instability may occur for no apparent reason.
In cases where I suspect GPPI is making a data link act up I will insert a low value resistor into the signal ground connection at one end and measure for 60 Hz voltage across the resistor. Experience has shown that as little as 2 volts GPPI can affect the stability of a high speed RS-232 link.
More Articles by BigDumbDinosaur
Have you tried Searching this site?
Unix/Linux/Mac OS X support by phone, email or on-site: Support Rates
This is a Unix/Linux resource website. It contains technical articles about Unix, Linux and general computing related subjects, opinion, news, help files, how-to's, tutorials and more. We appreciate comments and article submissions.
Many of the products and books I review are things I purchased for my own use. Some were given to me specifically for the purpose of reviewing them. I resell or can earn commissions from the sale of some of these items. Links within these pages may be affiliate links that pay me for referring you to them. That's mostly insignificant amounts of money; whenever it is not I have made my relationship plain. I also may own stock in companies mentioned here. If you have any question, please do feel free to contact me.
Specific links that take you to pages that allow you to purchase the item I reviewed are very likely to pay me a commission. Many of the books I review were given to me by the publishers specifically for the purpose of writing a review. These gifts and referral fees do not affect my opinions; I often give bad reviews anyway.
We use Google third-party advertising companies to serve ads when you visit our website. These companies may use information (not including your name, address, email address, or telephone number) about your visits to this and other websites in order to provide advertisements about goods and services of interest to you. If you would like more information about this practice and to know your choices about not having this information used by these companies, click here.
Click here to add your comments
What kind of UPS do you recommend? Currently we use APC UPS's, and have been lucky so far. Also, has anyone made a claim to APC for any UPS's that have been hit and got the money?
- Bruce Garlock
See http://aplawrence.com/Blog/B998.html for a comment by BigDumbDinosaur
"The entire computer system -- UNIX server, terminals, a PC, modem and the APC UPS -- were ruined."
Hey, Tony. Can you fix the grammar in that sentence, please?
--BigDumbDinosaur
---July 21, 2004
Wrong with that what is? Were to change it as you desire, tell me, and it done by me that manner. OK?
--TonyLawrence
You sound like one of my clients trying to describe how his PC is behaving after munching on a bagel.
--BigDumbDinosaur
---July 21, 2004
Bagels? In Illinois? I think not. They may THINK they are munching on Bagels, but folks around here know better :-)
--TonyLawrence
Hey now! We have some darn good Jewish delis in the Chicago area, well-stocked with all sorts of excellent bagels, along with my favorite, kosher corn beef. In fact, other than Chicago, New York is the only place I know of where top-of-the-line kosher corn beef can be gotten. Right now, I can picture about 1-1/2 inches of the stuff piled on some rye bread, with a thick chocolate malt to wash it down (the malt, of course, making the combination non-kosher).
Anyhow, my bagel reference was supposed to be a weak pun on one of the Windows maladies that is currently circulating around on the 'Net.
--BigDumbDinosaur
---July 22, 2004
Yeah, those darn Bagel viruses are driving me nuts. The things come so fast nowadays, I usuallly get one or two people caught before their virus software has updated.
Windows is so much fun..
--TonyLawrence
Don't miss responses! Subscribe to Comments by RSS or by Email
Click here to add your comments
If you want a picture to show with your comment, go get a Gravatar